Chiller and CDU Selection for Data Centers: A Practical Engineering Primer

In a liquid-cooled or hybrid data center, the chiller plant and the rack-level cooling system cannot be treated as separate equipment packages. The operating temperatures, flow requirements, redundancy strategy, and controls at one end of the system directly affect the other. 

That makes chiller and Cooling Distribution Unit (CDU) selection an interface problem as much as an equipment-selection problem. 

Part 1: Chiller Selection

Look Beyond Full-Load Efficiency 

 

Data centers operate continuously, but the cooling load and ambient conditions still change. Part-load efficiency, turndown, minimum-load stability, sequencing, and redundancy can have as much influence on annual performance as the full-load rating. 

Establish and Refine Water Temperature Requirements 

Traditional air-side cooling and rack-level liquid cooling may operate at different water temperatures, making temperature coordination an important consideration in data center design. Initial operating temperatures should be established based on the anticipated IT equipment requirements and cooling system architecture, then refined as equipment selections and system specifications are finalized. 

In mixed air- and liquid-cooled environments, separate water loops, heat exchangers, or temperature reset strategies may be necessary to accommodate different operating conditions while maintaining overall system efficiency and reliability. 

ASHRAE TC 9.9’s Thermal Guidelines for Data Processing Environments identifies facility-water temperature classes for liquid-cooled IT equipment, including W17, W27, W32, W40, W45, and W+. For example, W27 specifies a maximum facility-water supply temperature of 27°C (80.6°F), while W40 allows up to 40°C (104°F). These classifications provide a useful reference when evaluating cooling-system requirements, although final operating temperatures must align with the selected IT equipment and system design. 

 

Coordinate Heat Rejection With the Plant 

Cooling towers, dry coolers, fluid coolers, and adiabatic systems each create different tradeoffs in energy, water use, climate dependence, maintenance, and economization potential. The heat-rejection strategy should be evaluated with the chiller and facility-water temperatures rather than as a standalone selection. 

 

Part 2: CDU Selection 

 

The CDU is the bridge between the facility-water system and the technology-cooling system serving the IT equipment. Selection should start with the actual conditions on both sides of that interface. 

With DDC Solutions and Chilldyne now part of the Daikin Applied family, the broader portfolio brings together technologies spanning central-plant cooling, cooling distribution units, and high-density rack enclosures. This relationship provides an opportunity for closer coordination across equipment interfaces as data center cooling requirements continue to evolve. 

 

Key CDU Inputs 

  • Facility-water supply and return temperatures. 
  • Available differential pressure and required flow. 
  • Technology-cooling-system supply and return temperatures. 
  • Coolant chemistry and materials compatibility. 
  • Heat-exchanger approach and allowable approach temperature. 
  • Pump or pressure-control architecture. 
  • Filtration, monitoring, controls, and leak-management requirements. 
  • Current load plus a defined strategy for future expansion. 

 

Common Coordination Risks 

Problems arise when the plant and CDU are specified independently. A CDU may be capable of the required heat transfer on paper but unable to deliver the required technology-cooling-system temperature at the actual facility-water condition. Likewise, a plant optimized around one water temperature may lose efficiency if it must be reset to satisfy an uncoordinated rack-level selection. 

 

Treat Measurement and Commissioning as Part of the Design 

Flow, temperature, pressure, and BTU measurement provide the data needed to verify performance and diagnose issues after startup. Defining those points during design can make commissioning and ongoing optimization much more useful. 

 

Where AirReps Can Help 

AirReps works with engineers, owners, and contractors to support equipment selection and manufacturer coordination for data center cooling applications. Our portfolio includes central-plant cooling solutions from Daikin Applied, heat rejection equipment from BAC, cooling distribution units from Chilldyne, and high-density rack enclosures and containment solutions from DDC Solutions. 

Additional capabilities include airflow measurement from EBTRON and flow and energy measurement solutions from ONICON. As data center cooling requirements evolve, our team can help project stakeholders evaluate available equipment options and connect with manufacturer expertise to support project-specific needs.  

 


Contact AirReps to discuss central-plant cooling equipment and liquid cooling solutions for your data center application. 